EL
ErrorLib
Brands
||
  1. Home
  2. Schneider Electric
  3. Altivar 312 Variable Frequency Drive
  4. SLF
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

SLF

Modbus Fault

Schneider Electric · Altivar 312 Variable Frequency Drive

What does SLF mean?

This fault signals an interruption in communication on the Modbus bus, preventing the drive from exchanging data with a Modbus master or remote display terminal. Causes often include physical bus issues or a disconnected remote display terminal when HMI command is enabled. This results in a loss of external control, monitoring, or parameter access.

Common Causes

  • Broken, disconnected, or improperly wired RS-485 Modbus communication cable (e.g., A/B lines reversed or open).
  • Incorrect Modbus slave address (Parameter P5-01) or baud rate (Parameter P5-02) configured in the drive or Modbus master.
  • Missing or incorrectly placed 120 Ohm termination resistors at the physical ends of the Modbus bus segment.
  • Excessive electrical noise or electromagnetic interference (EMI) on the communication lines, corrupting data packets.
  • Modbus master controller experiencing a communication timeout or not actively polling the drive.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Inspect the RS-485 Modbus communication cable for physical damage, loose connections, or incorrect wiring (e.g., A to A, B to B) at both the drive and master ends.

  2. 2

    2. Verify that the drive's Modbus slave address (Parameter P5-01) and baud rate (Parameter P5-02) match the configuration settings in the Modbus master controller.

  3. 3

    3. Check for the correct installation of 120 Ohm termination resistors at the two furthest physical ends of the Modbus bus segment.

  4. 4

    4. Measure the voltage differential between the Modbus A and B lines (should fluctuate between 0-5VDC during communication) using an oscilloscope or specialized Modbus tester.

  5. 5

    5. Ensure that no other device on the Modbus network is using the same slave address as the drive, causing address conflicts.

Browse all codes in this manual (31)
Verified technical data. Last updated: April 2026

Related Faults

A-17Alarm Button (Remote Display)CFFIncorrect ConfigurationCFIInvalid Configuration
Source: Schneider Electric Altivar 312 Variable Frequency Drive
View Official PDFSearch more codes in this manual