SCF

Motor Short-Circuit

Schneider Electric · ALTIVAR 28 Variable Speed Drive

What does SCF mean?

This fault signals a short-circuit or ground fault condition detected at the output of the drive controller or within the motor windings. This is a critical fault that can cause immediate and significant damage to the drive's output stage if not addressed.

Common Causes

  • Motor cable insulation breakdown leading to phase-to-phase or phase-to-ground short circuit.
  • Internal motor winding short circuit (turn-to-turn or phase-to-ground).
  • Contamination (e.g., conductive dust, moisture) in motor terminal box or drive output terminals.
  • Damage to drive output power components (e.g., IGBTs) causing a false short circuit detection.
  • Motor cable length exceeding recommended maximum for the drive, increasing capacitance and leakage current.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Disconnect motor cables from drive output terminals (U, V, W).

  2. 2

    2. Perform insulation resistance test on motor windings to ground and between phases at 500VDC (typical minimum 100MΩ).

  3. 3

    3. Measure resistance between motor output terminals U, V, W on the drive; values should be infinite if motor is disconnected.

  4. 4

    4. Visually inspect drive output terminals and motor terminal box for signs of arcing, carbon tracking, or contamination.

  5. 5

    5. Check continuity of motor cables from drive end to motor end for each phase (U to U, V to V, W to W) using a multimeter.