CrF

Capacitor precharge fault

Schneider Electric · ATV32HD11N4 Variable Speed Drive

What does CrF mean?

A fault related to the capacitor precharge circuit, either due to a control issue with the precharge relay or a damaged precharge resistor. This fault prevents the drive from powering up correctly, indicating a critical internal hardware failure.

Common Causes

  • Failure of the precharge relay (K1) to close or open correctly during power-up sequence.
  • Damaged or open-circuit precharge resistor (R_PC) preventing DC bus charging.
  • Control circuit malfunction preventing activation of the precharge relay coil.
  • Short circuit in the DC bus capacitance (rare but can prevent proper precharge).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Disconnect input power (L1, L2, L3) and measure the resistance of the precharge resistor (R_PC) within the drive.

  2. 2

    2. Verify the voltage supplied to the precharge relay coil (e.g., 24VDC) during the power-up sequence.

  3. 3

    3. Visually inspect the precharge relay contacts for signs of pitting, burning, or welding.

  4. 4

    4. Measure the DC bus voltage across the positive and negative terminals after power-up attempt to confirm precharge sequence failure.

  5. 5

    5. If accessible, inspect main capacitors for signs of bulging or leakage, indicating internal damage.

Browse all codes in this manual (25)
Verified technical data. Last updated: March 2026

Related Faults

Source: Schneider Electric ATV32HD11N4 Variable Speed Drive