F26

AI Under Frequency

Schneider Electric · XW Pro NA Operation Guide

What does F26 mean?

This fault indicates an under-frequency condition detected by the anti-islanding protection. This mechanism ensures the inverter disconnects from the grid if grid power is unstable or absent, preventing dangerous backfeeding and potential damage to equipment.

Common Causes

  • Grid supply frequency dropping below the inverter's configured lower threshold (e.g., 49.5 Hz or 59.5 Hz) for the anti-islanding protection.
  • Grid instability, excessive demand, or localized power generation issues causing a sustained frequency dip.
  • Inverter's internal frequency measurement circuit experiencing drift or failure, leading to an erroneous under-frequency detection.
  • Anti-islanding parameter P_AI_Freq_Low set too close to the nominal grid frequency, making the system overly sensitive.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Using a true RMS multimeter with frequency measurement, monitor the incoming grid frequency at the inverter's AC input terminals (e.g., L1-L2) over a 15-minute period.

  2. 2

    Compare the recorded frequency against the inverter's configured anti-islanding low-frequency trip point (e.g., Parameter P_AI_Freq_Min).

  3. 3

    Inspect the integrity of the AC voltage sensing connections on the inverter's input terminals for any signs of corrosion or looseness.

  4. 4

    If measured grid frequency is stable and within limits, consider decreasing the anti-islanding under-frequency threshold (e.g., Parameter P_AI_Freq_Min by 0.2 Hz) only if compliant with local grid codes.

  5. 5

    If the fault persists despite stable grid and parameter adjustments, initiate an inverter self-diagnostic routine to assess the internal frequency measurement hardware.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults

Source: Schneider Electric XW Pro NA Operation Guide