Schneider Electric · XW Pro NA Operation Guide
This Escalating Automatic Fault indicates an AC under-voltage shutdown (below 108 V). If it occurs 3 times in 2 minutes, it becomes a manual fault, meaning the inverter has repeatedly shut down to protect connected loads.
Click steps to track your progress.
Measure AC output voltage at inverter terminals L1, L2, L3 (or L1, N for single phase) using a true RMS multimeter while applying a controlled load.
Verify inverter output voltage configuration (e.g., Parameter P3-10, P3-11) against system requirements and local grid standards.
Inspect AC output wiring for correct gauge sizing according to NEC/IEC standards and potential loose terminations at the inverter, contactor, and load.
Monitor utility grid incoming voltage at the inverter input terminals (L1, L2, L3, N) using a power quality analyzer to detect brownout conditions below 108V.
Check for high resistance across AC output contactor poles or circuit breaker terminals by measuring voltage drop when current is flowing (should be < 0.1V).