27

No Limit Switches / Limit Switch Error

SEW Eurodrive · MOVIDRIVE compact System (MCF/MCV/MCS4_A)

What does 27 mean?

Emergency stop because both hardware limit switches are either missing/open circuit, or they are incorrectly wired in relation to the motor's direction of rotation. This prevents the drive from accurately detecting its travel limits.

Common Causes

  • Limit switch not detected by the system.
  • Limit switch wiring is open or shorted.
  • Limit switch is physically obstructed and not actuating.
  • Configuration error: limit switch inputs not assigned.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Check the wiring of both limit switches for proper connection and continuity.

  2. 2

    Swap the limit switch connections if they are found to be inverted relative to the motor's direction of rotation.

  3. 3

    Reprogram the terminal assignments and logic for the limit switches if the configuration is incorrect.