The inverter has detected that the output current exceeded 185% of the rated output current for more than 60 milliseconds. This indicates a significant overload on the motor or a short circuit in the output wiring. This will cause an immediate switch-off of the inverter to prevent damage to the motor or the drive.
Click steps to track your progress.
Immediately disconnect the motor from the inverter output terminals (U, V, W).
With the motor disconnected, measure insulation resistance of the motor windings to ground (e.g., 500VDC megohmmeter, expected >100M Ohm).
Measure the resistance between each output phase (U-V, V-W, W-U) of the motor with a multimeter to detect a short circuit (expected typically <1 Ohm but balanced).
Inspect the motor cables and connections (terminals, junction boxes) for signs of damage, chafing, or arcing that could indicate a short.
Power up the inverter with the motor disconnected and attempt a test run without a load; if the F01 persists, the inverter's output stage is likely faulty.