SEW Eurodrive · MOVIFIT-FC Inverter
The DC link voltage has exceeded its permissible limit. Potential causes include a ramp time set too short, incorrect wiring or internal resistance of the brake coil/braking resistor, thermal overload in the braking resistor, or an invalid mains voltage range. High DC link voltage poses a risk to the inverter's components.
Click steps to track your progress.
Increase the ramp time setting in the inverter parameters.
Check the connection between the braking resistor and the brake coil and correct it.
Check the internal resistance of the brake coil/braking resistor, referring to the "Technical Data" section of the manual for expected values.
Check the mains voltage to ensure it is within the valid operating voltage range for the unit.
Reset the fault by switching off the DC 24 V supply voltage.