26

External terminal

SEW Eurodrive · MOVIFIT-FC Inverter

What does 26 mean?

A low signal was detected on the external terminal that has been programmed with the "/External fault" function. This condition is specific to SBUS slave units and indicates a problem with an external monitoring circuit.

Common Causes

  • External digital input fault or configuration error.
  • Unexpected signal on a designated external terminal.
  • Parameter P0700 (digital input assignment) misconfiguration.
  • External interlock signal failure.
  • Wiring issue with external control terminals.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the signal level at the specified external terminal.

  2. 2

    Reset the fault by switching off the DC 24 V supply voltage.

Browse all codes in this manual (26)