SEW Eurodrive · MOVIMOT MM..C
This fault occurs when the DC link voltage exceeds its safe operating limits. This condition can be caused by regeneration from the motor, short ramp times, or issues with the braking resistor configuration.
Click steps to track your progress.
Increase the ramp time setting.
Check the connection between the braking resistor and brake coil for integrity.
Check the internal resistance of the brake coil/braking resistor (refer to the "Technical Data" section of the manual).
Verify the braking resistor size is appropriate for the application's energy requirements.
Switch off the 24 VDC supply voltage to reset the fault.
Issue a reset command via MOVILINK®.