SEW Eurodrive · MOVIMOT MM..D With AC Motor DRS
A communication timeout occurred during cyclical communication via the RS-485 interface. Upon this error, the drive will decelerate and stop along its set ramp. Communication must be re-established to re-enable the drive.
Click steps to track your progress.
Check and establish the communication link between the RS-485 master and MOVIMOT® inverter
Verify the number of slaves connected to the RS-485 master, ensuring it does not exceed 8 MOVIMOT® inverters for cyclical communication with a 1-second timeout interval
Reset the error by switching off the DC 24 V supply voltage
Reset the error via the control system or dedicated reset function