SEW Eurodrive · MOVIMOT MM..D With AC Motor DRS
The drive has operated at its set current limit for longer than 500 ms when additional function 2 (adjustable current limitation) is active and the monitoring function is in effect (above 15 Hz). This indicates the motor is drawing too much current.
Click steps to track your progress.
Check the current limit setting using switch f2 on S2 (detent settings 0-10 correspond to 90-160% of IN) and adjust if appropriate for the application
Reduce the load on the drive to prevent current limit activation
Verify the minimum frequency (2 Hz for RS-485 control) and setpoint f2 (5 Hz for binary control) are correctly configured