An immediate switch-off with inhibit occurs due to a ground fault. This can be caused by a ground fault in the motor, the inverter itself, or the motor supply lead. It may also be a symptom of an overcurrent condition.
Click steps to track your progress.
Replace the motor if a ground fault is detected within it
Replace the MOVITRAC® B inverter if it has an internal ground fault
Eliminate any ground fault found in the motor supply lead
Refer to troubleshooting steps for F01 if overcurrent is a contributing factor