36
Option missing
SEW Eurodrive · MCBSM
What does 36 mean?
Immediate switch-off with inhibit. This fault occurs if an incorrect option card is used, the setpoint/control signal source or operating mode is not permitted for the option card, or a required option is entirely missing. This prevents proper system functionality and operation, necessitating a restart after correction.
Common Causes
- A required option module is not physically installed or detected.
- Option slot is empty where a module is expected by configuration.
- Faulty connection of the option module.
- Configuration parameter (e.g., P1-02) expects an option that is not present.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Use the correct option card compatible with the unit.
- 2
Set the correct setpoint source, control signal source, or operating mode according to the application.
- 3
Check parameters P120 and P121 for FBG11B, and P120 and P642 for FIO12B, to ensure required options are present and correctly configured.
Verified technical data. Last updated: March 2026
Related Faults
Source: SEW Eurodrive MCBSM