Siemens · DAsl Diagnostics and Alarms
The Sensor Module's existing software and/or hardware is not compatible with the higher-level control's safe motion monitoring function. This prevents the safe motion monitoring features from functioning correctly, potentially impacting safety-critical operations. Note that this specific fault does not immediately result in a safety stop response.
Click steps to track your progress.
Compare the installed firmware version of the Sensor Module with the required version for the safety control unit.
Update the Sensor Module firmware to a compatible version using STARTER or TIA Portal software.
Verify the hardware revision number of the Sensor Module and confirm its compatibility with the overall safety system documentation.
Check the order number (MLFB) of the Sensor Module against the project design specifications.
Re-compile and download the safety program to the control unit after ensuring compatible module versions are configured.