Siemens · DCM
The downloaded parameterization file is incompatible with the currently installed module type (e.g., different Order No. or MLFB). This means the configuration settings do not match the hardware, preventing correct operation. Operating with an incompatible configuration can lead to erratic behavior or inability to start.
Click steps to track your progress.
Verify the exact Order Number (MLFB) of the installed drive control unit and power unit against the project documentation.
Compare the firmware version of the control unit (e.g., P0000 value) with the firmware version used to generate the parameter file.
Reload the parameter file that specifically matches the installed hardware components' Order Numbers and firmware versions.
If a parameter file cannot be located, perform a hardware configuration scan (e.g., in TIA Portal or STARTER) and generate a new parameter set.
Check all configured peripheral modules (e.g., TM15, CX32) are physically present and connected correctly to the drive control unit.