Siemens · FC1765DC Controller
An internal fault has been detected within Absolute Encoder 1 (EnDat), as indicated by set bits in its fault word. This can signify issues such as a failed lighting system, low signal amplitude, incorrect position values, or problems with the encoder's 5V power supply (overvoltage, undervoltage, overcurrent). If applicable, it could also mean the encoder battery needs replacement.
Click steps to track your progress.
1. Measure the power supply voltage at the encoder connector (e.g., Pin 1 and Pin 2) using a multimeter to verify it is within specification (e.g., 5VDC ±5%).
2. Inspect the EnDat encoder cable (e.g., connected to socket X21) for physical damage, proper shielding continuity, and secure connections.
3. Access the drive diagnostics and monitor the encoder's internal fault word (r2520) for specific sub-error indications (e.g., lighting, amplitude).
4. Power down the system, disconnect and then securely reconnect the encoder cable at both ends to ensure proper electrical contact.
5. If available, temporarily replace Encoder 1 with a known good EnDat encoder to isolate whether the fault is with the encoder or the drive's input.