EL
ErrorLib
Brands
||
  1. Home
  2. Siemens
  3. FC1765DC Controller
  4. 240003
About·Privacy·Terms

ErrorLib — Industrial Fault Code Library

Disclaimer: ErrorLib is an independent technical reference tool. While we aim for accuracy, always verify with the manufacturer’s official service manuals before performing maintenance on industrial equipment. ErrorLib is not affiliated with the brands listed.

240003

Fault at DRIVE-CLiQ Socket X103

Siemens · FC1765DC Controller

What does 240003 mean?

A fault has been detected at the drive object connected to DRIVE-CLiQ socket X103. The fault value (r0949) will indicate the first specific fault that occurred for this connected drive object. This generic fault requires further investigation of the device attached to X103.

Common Causes

  • Physical damage to the DRIVE-CLiQ cable connected to socket X103 or a loose connection at either end.
  • Internal hardware fault within the specific DRIVE-CLiQ component (e.g., Motor Module, Sensor Module) connected to X103.
  • Interruption or severe fluctuation of the 24VDC power supply to the DRIVE-CLiQ component connected at X103.
  • Incorrect DRIVE-CLiQ topology configuration or missing component definition for the device connected to X103.
  • Electromagnetic interference affecting the DRIVE-CLiQ communication signals due to improper cable routing or shielding.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Note the specific fault value (r0949) to understand the detailed fault condition of the DRIVE-CLiQ object at X103.

  2. 2

    2. Power cycle the entire drive system and the specific DRIVE-CLiQ component connected to socket X103.

  3. 3

    3. Inspect the DRIVE-CLiQ cable connected to X103 for physical damage (kinks, cuts) and ensure it is securely seated.

  4. 4

    4. Measure the 24VDC power supply at the connected DRIVE-CLiQ component to confirm stable and correct voltage levels.

  5. 5

    5. Swap the DRIVE-CLiQ cable with a known good, identical cable to rule out cable integrity issues.

  6. 6

    6. If possible, connect a different, known good DRIVE-CLiQ component to socket X103 to determine if the fault is with the component or the drive port.

Browse all codes in this manual (28)
Verified technical data. Last updated: April 2026

Related Faults

201630SI CU: Brake Control Error201673SI Motion: Sensor Module software/hardware incompatible201680SI Motion CU: Checksum error safety monitoring functions
Source: Siemens FC1765DC Controller
View Official PDFSearch more codes in this manual