Siemens · FC1765DC Controller
An alarm has been detected at the drive object connected to DRIVE-CLiQ socket X100. The alarm value (r2124) will indicate the first specific alarm that occurred for this connected drive object. This generic alarm indicates a warning condition that warrants further investigation of the device attached to X100.
Click steps to track your progress.
1. Read the specific alarm value (r2124) from the DRIVE-CLiQ object connected to X100 for detailed diagnostic information.
2. Inspect the DRIVE-CLiQ cable connected to X100 for physical integrity, secure connections, and proper shielding.
3. Verify the 24VDC power supply at the connected DRIVE-CLiQ component for stability and correct voltage levels (e.g., 24VDC ±10%).
4. Perform a DRIVE-CLiQ topology comparison (P0990 = 1) to ensure the actual physical configuration matches the configured setup.
5. Check the diagnostics and parameter settings of the connected DRIVE-CLiQ component itself for any active alarms or warnings.