Siemens · FC1765DC Controller
A fault has occurred during the test stop procedure on the Motor Module (MM) side, specifically related to the evaluation of states for Fail-safe Digital Outputs (F-DOs). This indicates that the expected states of the DOs or diagnostic DOs were not fulfilled, or an internal timer/state issue occurred, often a mismatch between expected and read-back signals during a test state.
Click steps to track your progress.
1. Identify the specific F-DO (e.g., F-DO1, F-DO2) that failed the test by reviewing internal safety diagnostics (r9625).
2. Measure the voltage at the output terminals of the problematic F-DO (e.g., X126/1, X126/2) on the MM during a test stop sequence.
3. Disconnect the external load from the problematic F-DO and re-run the test stop procedure to isolate internal vs. external fault.
4. Verify the wiring continuity and insulation resistance (using a megohmmeter) of the cable connected to the F-DO.
5. Review parameter settings for F-DO test stop (e.g., P9620, P9621) and ensure they align with the safety application requirements.
6. If the fault persists with no external load, consider replacing the Motor Module after thorough diagnostics.