F07936

Drive: load failure

Siemens · DCM

What does F07936 mean?

The load monitoring function has detected a significant failure in the mechanical load connected to the drive. This indicates a deviation from expected load conditions, potentially caused by a broken belt, coupling, or other mechanical issue in the driven machinery. If unaddressed, this can lead to production downtime or further mechanical damage.

Common Causes

  • Broken mechanical component in the load (e.g., belt, gearbox shaft, coupling) causing the motor to run freely or with reduced resistance.
  • Loss of mechanical coupling between the motor and the load (e.g., keyway sheared, setscrew loose).
  • Incorrectly configured load monitoring parameters (e.g., P0595 (Load monitoring threshold), P0596 (Load monitoring delay)) leading to false trips.
  • A sensor providing load feedback (e.g., torque sensor) has failed or is giving erroneous readings.
  • Overload condition causing the motor to stall or significantly reduce speed while drawing high current, interpreted as 'load failure'.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Inspect the mechanical load system (belts, gears, couplings, bearings) for any signs of breakage, jamming, or disengagement.

  2. 2

    2. Monitor motor current (r0027), motor torque (r0031), and motor speed (r0021) to identify any sudden drops or unexpected fluctuations in load.

  3. 3

    3. Verify the settings of load monitoring parameters (e.g., P0595 (Load monitoring threshold), P0596 (Load monitoring delay)) are appropriate for the application.

  4. 4

    4. Check the integrity of any external load sensors (e.g., torque transducer) if used, by verifying their output signal.

  5. 5

    5. Perform a manual jog or slow run of the motor and load, observing for unusual noises, vibrations, or free movement indicating a disconnected load.

Browse all codes in this manual (60)
Verified technical data. Last updated: March 2026

Related Faults