240004

Fault at DRIVE-CLiQ Socket X104

Siemens · FC1765DC Controller

What does 240004 mean?

A fault has been detected at the drive object connected to DRIVE-CLiQ socket X104. The fault value (r0949) will indicate the first specific fault that occurred for this connected drive object. This generic fault requires further investigation of the device attached to X104.

Common Causes

  • Physical damage to the DRIVE-CLiQ cable connected to socket X104 or a loose connection at either end.
  • Internal hardware fault within the specific DRIVE-CLiQ component (e.g., Motor Module, Sensor Module) connected to X104.
  • Interruption or severe fluctuation of the 24VDC power supply to the DRIVE-CLiQ component connected at X104.
  • Incorrect DRIVE-CLiQ topology configuration or missing component definition for the device connected to X104.
  • Electromagnetic interference affecting the DRIVE-CLiQ communication signals due to improper cable routing or shielding.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Note the specific fault value (r0949) to understand the detailed fault condition of the DRIVE-CLiQ object at X104.

  2. 2

    2. Power cycle the entire drive system and the specific DRIVE-CLiQ component connected to socket X104.

  3. 3

    3. Inspect the DRIVE-CLiQ cable connected to X104 for physical damage (kinks, cuts) and ensure it is securely seated.

  4. 4

    4. Measure the 24VDC power supply at the connected DRIVE-CLiQ component to confirm stable and correct voltage levels.

  5. 5

    5. Swap the DRIVE-CLiQ cable with a known good, identical cable to rule out cable integrity issues.

  6. 6

    6. If possible, connect a different, known good DRIVE-CLiQ component to socket X104 to determine if the fault is with the component or the drive port.

Browse all codes in this manual (28)
Verified technical data. Last updated: March 2026

Related Faults

Source: Siemens FC1765DC Controller