F07807

Drive: Short-circuit/ground fault detected

Siemens · SINAMICS G120C Variable Speed Drive

What does F07807 mean?

A phase-to-phase short-circuit or a ground fault has been detected at the motor-side output terminals of the converter. The fault value specifies the exact short-circuit type or ground fault with current component. This is a critical electrical fault that can cause immediate and severe damage to the power module or motor, necessitating rapid isolation and repair to prevent costly failures and prolonged downtime.

Common Causes

  • Phase-to-phase short circuit in the motor winding or motor cable insulation breakdown.
  • Ground fault in the motor winding, motor cable, or motor itself due to insulation failure or moisture ingress.
  • Water ingress or condensation causing a short circuit path in the motor terminal box or cable glands.
  • Incorrect motor parameters (e.g., P0304, P0305) configured in the drive, leading to misinterpretation of motor current.
  • Damage to the power unit's output stage (e.g., IGBT failure) causing a short circuit at the drive's terminals.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect the motor cables from the drive's output terminals (e.g., U, V, W) and measure the resistance between phases and from each phase to ground using a megohmmeter (insulation tester).

  2. 2

    Inspect the motor cables for any physical damage to insulation, crimping, or signs of overheating along their entire length.

  3. 3

    Verify the motor's internal winding resistance and compare it to the manufacturer's specifications (e.g., using an LCR meter).

  4. 4

    Check the motor terminal box for moisture, debris, or loose connections that could cause a short circuit.

  5. 5

    If the motor and cables test good, the fault lies within the power unit's output stage, requiring power unit replacement.

Browse all codes in this manual (34)
Verified technical data. Last updated: March 2026

Related Faults

Source: Siemens SINAMICS G120C Variable Speed Drive