A00523

Output fault

Siemens · SINAMICS G120

What does A00523 mean?

This alarm indicates that one phase of the inverter's output is disconnected, suggesting a break in the power path to the motor. This condition can lead to motor malfunction, reduced performance, or potential damage if operated under unbalanced conditions.

Common Causes

  • Disconnection or high resistance in one of the motor phases (U, V, W) between the inverter output terminals and the motor.
  • Internal power semiconductor (IGBT) failure or damage in one phase of the inverter bridge.
  • Motor winding open circuit or inter-turn short in one phase, causing an imbalanced load detected by the drive.
  • Faulty motor cable or terminal connection, resulting in a loss of connection to one phase at the drive or motor side.
  • Incorrect motor parameterization (e.g., P0304 - motor rated current) leading to an inability for the drive to detect the motor properly.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. De-energize the drive and measure the resistance of each motor phase (U-V, V-W, W-U) at the motor terminals; compare readings to specifications.

  2. 2

    2. With power off, check all output cable connections for the motor (U, V, W) at both the inverter terminals and the motor terminal box for tightness and corrosion.

  3. 3

    3. Measure the insulation resistance of each motor phase to ground and between phases using a megohmmeter (e.g., 500VDC or 1000VDC test voltage).

  4. 4

    4. Verify the motor parameters (e.g., P0304, P0305, P0307, P0310) configured in the drive match the motor nameplate data exactly.

  5. 5

    5. If using an output filter or reactor, inspect its connections and internal integrity for any signs of damage or open circuits.

  6. 6

    6. Observe drive current output (e.g., r0027) on each phase using a clamp meter during a low-speed run to detect current imbalance.

Browse all codes in this manual (109)
Verified technical data. Last updated: April 2026