Siemens · SINAMICS G120C Variable Speed Drive
The alarm threshold for the rectifier's overtemperature has been reached, indicating excessive heat generation in the input rectifier stage. This can be due to overload or cooling issues. If the rectifier temperature rises by an additional 5 K, it will trigger fault F30037, potentially causing the drive to trip and risking damage to the rectifier components.
Click steps to track your progress.
Measure input AC line current (r0068) and compare to the drive's input rating (P0206) to identify potential overload.
Check for proper operation of all internal cooling fans by observing rotation and listening for fan noise.
Inspect the rectifier heatsink for dust buildup and clean thoroughly with compressed air (ensure power is off).
Measure the AC supply voltage (r0067) and check for voltage imbalances across phases using a multimeter.
Verify that the drive's load profile does not exceed the continuous rating of the rectifier stage for extended periods.