Frequencies detected on the DC link voltage suggest line asymmetry or the failure of a line or motor phase. If this alarm persists, it will eventually trigger fault F30011 after a specific duration. This condition causes imbalanced currents, increased losses, and premature component wear, and if unresolved, will lead to a drive trip, interrupting operation.
Click steps to track your progress.
Measure the line-to-line voltages (L1-L2, L2-L3, L3-L1) at the drive's input terminals (e.g., X10/X100 terminals) using a multimeter.
Check all input fuses and circuit breakers upstream of the drive for continuity and proper function.
Inspect the input wiring for loose connections or damaged conductors at the main terminals.
Verify the line reactor's inductance and inspect for visible damage or overheating if present in the input circuit.
Monitor parameter r0025 for incoming line voltage values to confirm stability and balance.