F07807

Drive: Short-circuit/ground fault detected

Siemens · SINAMICS G120C Variable Speed Drive

What does F07807 mean?

A phase-to-phase short-circuit or a ground fault has been detected at the motor-side output terminals of the converter. The fault value specifies the exact short-circuit type or ground fault with current component. This is a critical electrical fault that can cause immediate and severe damage to the power module or motor, necessitating rapid isolation and repair to prevent costly failures and prolonged downtime.

Common Causes

  • Phase-to-phase short circuit in the motor winding or motor cable insulation breakdown.
  • Ground fault in the motor winding, motor cable, or motor itself due to insulation failure or moisture ingress.
  • Water ingress or condensation causing a short circuit path in the motor terminal box or cable glands.
  • Incorrect motor parameters (e.g., P0304, P0305) configured in the drive, leading to misinterpretation of motor current.
  • Damage to the power unit's output stage (e.g., IGBT failure) causing a short circuit at the drive's terminals.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Disconnect the motor cables from the drive's output terminals (e.g., U, V, W) and measure the resistance between phases and from each phase to ground using a megohmmeter (insulation tester).

  2. 2

    Inspect the motor cables for any physical damage to insulation, crimping, or signs of overheating along their entire length.

  3. 3

    Verify the motor's internal winding resistance and compare it to the manufacturer's specifications (e.g., using an LCR meter).

  4. 4

    Check the motor terminal box for moisture, debris, or loose connections that could cause a short circuit.

  5. 5

    If the motor and cables test good, the fault lies within the power unit's output stage, requiring power unit replacement.