Siemens · SINAMICS G120C Variable Speed Drive
A phase-to-phase short-circuit or a ground fault has been detected at the motor-side output terminals of the converter. The fault value specifies the exact short-circuit type or ground fault with current component. This is a critical electrical fault that can cause immediate and severe damage to the power module or motor, necessitating rapid isolation and repair to prevent costly failures and prolonged downtime.
Click steps to track your progress.
Disconnect the motor cables from the drive's output terminals (e.g., U, V, W) and measure the resistance between phases and from each phase to ground using a megohmmeter (insulation tester).
Inspect the motor cables for any physical damage to insulation, crimping, or signs of overheating along their entire length.
Verify the motor's internal winding resistance and compare it to the manufacturer's specifications (e.g., using an LCR meter).
Check the motor terminal box for moisture, debris, or loose connections that could cause a short circuit.
If the motor and cables test good, the fault lies within the power unit's output stage, requiring power unit replacement.