F07810

Drive: Power unit EEPROM without rated data

Siemens · SINAMICS G120C Variable Speed Drive

What does F07810 mean?

No rated data is stored in the power unit's EEPROM, meaning the drive lacks essential operational parameters. Without this critical data, the power unit cannot be correctly configured, initialized, or operated. This fault renders the drive inoperable, as attempts to run it without appropriate parameters could lead to unpredictable behavior or damage.

Common Causes

  • New or replacement power unit installed without initial parameter transfer or default data loading into its EEPROM.
  • Corruption of the EEPROM data in the power unit, possibly due to power fluctuations during manufacturing or initial setup.
  • Incompatibility between the power unit hardware and the Control Unit, preventing automatic data transfer or recognition.
  • Incorrect service replacement or attempted firmware update on the power unit without proper data initialization.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the power unit's hardware version and ensure it is compatible with the installed Control Unit.

  2. 2

    Perform a factory reset of the drive parameters (P0010 = 30, P0970 = 1) to attempt to load default power unit data.

  3. 3

    Load a saved parameter set (e.g., from a memory card or previous backup) to the drive, ensuring it includes power unit specific data.

  4. 4

    If the fault persists on a new power unit, it may be defective and require replacement.