The air intake temperature in the power unit has exceeded the permissible limit, typically 55 °C. This condition signifies critical overheating of the incoming air, often caused by high ambient temperatures, insufficient airflow, or a fan failure. This fault forces an OFF1 or OFF2 reaction, stopping the drive, and cannot be acknowledged until the temperature falls below the alarm threshold of A05002.
Click steps to track your progress.
Measure the air intake temperature directly at the drive using a thermal sensor or calibrated thermometer.
Verify the operation of all control cabinet cooling fans and clean any clogged air filter mats.
Check for obstructions in the cabinet's exhaust path, ensuring hot air can escape freely.
Monitor the control cabinet's internal temperature and external ambient temperature over time using data loggers.
Review the drive's installation manual for correct mounting clearances and ambient temperature specifications.