F45

Device added (default param.)

Vacon · NXP AFE-II Drive

What does F45 mean?

An option board of a different type has been added to the drive, causing the drive to load default parameters. This indicates a change in hardware configuration that requires re-parameterization.

Common Causes

  • Installation of a new option board (e.g., I/O extension, fieldbus adapter, encoder feedback) into the drive.
  • Replacement of an existing option board with a different type or version.
  • Accidental removal and re-insertion of an option board, causing the drive to re-detect it.
  • Option board or drive control board failure causing incorrect identification of hardware.
  • Firmware incompatibility between the drive and the newly installed option board.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify that the newly installed option board is the correct type and compatible with the drive model and firmware version.

  2. 2

    If the option board was intentionally added, reload the application parameters from a backup file (e.g., using Drive Composer or control panel). The drive loaded defaults to protect against incorrect operation.

  3. 3

    If no new option board was added, cycle power to the drive. Remove and re-seat all existing option boards to ensure proper connection.

  4. 4

    If the fault persists without any hardware changes, the drive's control board or an existing option board may be faulty, causing misidentification.

  5. 5

    Check the drive's diagnostic messages for specific option board identification (e.g., Menu 15-XX 'Option board status') to pinpoint which slot/board is causing the detection event.

Browse all codes in this manual (34)
Verified technical data. Last updated: April 2026

Related Faults

F1Over current faultF10Line Synchronization FaultF11Line phase supervision
Source: Vacon NXP AFE-II Drive