A digital input configured for external fault monitoring has been activated, signaling a fault condition from an external device or system. This is a generic fault triggered by an external safety or monitoring circuit.
Click steps to track your progress.
Identify the specific digital input (e.g., DI1) configured as the external fault input using parameters like P2-01 (Digital Input 1 Function).
Visually inspect and verify the status of all external devices connected to the identified digital input.
Measure the voltage across the identified digital input terminal (e.g., DI1 to COM) to confirm the active state of the fault signal.
Trace the control wiring from the external device to the drive's digital input, checking for cable damage or loose connections.
Review the external device's status indicators or diagnostic messages to pinpoint the source of its fault condition.
Temporarily disconnect the external fault signal from the digital input (for troubleshooting only) to verify the drive's reaction.