F60

Cooling

Vacon · NXP AFE-II Drive

What does F60 mean?

For liquid-cooled units, this protection detects a failure in the cooling liquid circulation, typically via an external sensor connected to the Cooling Monitor digital input. It generates a warning when the drive is stopped and a fault (with a coast stop) when running. Continued operation without proper cooling will lead to severe overheating.

Common Causes

  • Insufficient flow rate of cooling liquid through the heat exchanger, detected by a flow switch connected to the Cooling Monitor input (e.g., DI6).
  • Failure of the cooling liquid pump (e.g., motor fault, impeller blockage) leading to a loss of circulation.
  • Blockage in the cooling liquid circuit (e.g., clogged filter, restricted piping) reducing flow.
  • Faulty external cooling monitor sensor (e.g., flow switch, pressure switch) providing an incorrect signal to the drive.
  • Air trapped in the cooling liquid loop, causing erratic flow and sensor activation.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect the cooling liquid circulation pump for operational status and proper rotation.

  2. 2

    Verify the state of the external cooling monitor sensor (e.g., flow switch) by manually actuating it or checking its electrical output (e.g., continuity).

  3. 3

    Check the cooling liquid level in the reservoir and confirm it is above the minimum required level.

  4. 4

    Measure the actual flow rate of the cooling liquid using an inline flow meter, comparing it to the system's specified minimum.

  5. 5

    Clean any accessible filters or strainers within the cooling liquid circuit to remove potential blockages.

  6. 6

    Bleed air from the cooling loop by following the equipment manufacturer's specific procedure.

Browse all codes in this manual (34)