Maintenance Counter 2 Alarm
Vacon · 100 FLOW Application Guide
What does 1303 mean?
Maintenance counter 2 has exceeded its programmed alarm limit, serving as an advisory to schedule or perform maintenance for the component it monitors. This is a pre-warning before a potential fault condition. Proactive maintenance is crucial to maintain optimal equipment performance and prevent unexpected downtime.
Common Causes
- Operating hours or cycles tracked by Maintenance Counter 2 (Parameter P7-03) have exceeded the programmed alarm threshold (Parameter P7-04).
- The programmed alarm limit for Maintenance Counter 2 (P7-04) is too conservative for the application's actual wear patterns.
- Preventative maintenance for the component linked to Counter 2 has been delayed beyond the advisory period.
- Incorrect configuration of Maintenance Counter 2 parameters leading to premature alarming.
Repair Steps & Checklist
Click steps to track your progress.
- 1
1. Identify the specific component or function monitored by Maintenance Counter 2 (e.g., motor bearing lubrication, fan replacement).
- 2
2. Perform the recommended preventative maintenance task associated with Maintenance Counter 2.
- 3
3. Reset Maintenance Counter 2 by setting parameter P7-03 to 0 (or via a dedicated maintenance function on the HMI).
- 4
4. Re-evaluate the alarm limit P7-04 and adjust it based on historical maintenance data and component lifespan expectations.
- 5
5. Log the maintenance performed, including the date and the new value of P7-03 after reset, for future reference.