Unbalance
Vacon · 100 FLOW Application Guide
What does 18 mean?
This is a warning (not a fault trip) indicating an unbalance between power modules in paralleled units. Subcodes specify if the unbalance is in current or DC-Voltage.
Common Causes
- Unequal current sharing between parallel power modules in a multi-drive setup.
- Mismatch in impedance between parallel power paths.
- Failure or derating of one or more power modules.
- Incorrect load balancing configuration.
- Control loop instability affecting current distribution.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Verify impedance matching for all parallel power modules.
- 2
Measure current output from each individual power module if possible.
- 3
Check status of individual power modules for any signs of failure or derating.
- 4
Confirm parameter settings for parallel operation are correctly applied to all drives.
- 5
Ensure load distribution is balanced across all connected modules.