50

Analog Input Low Fault

Vacon · 100 FLOW Application Guide

What does 50 mean?

One or more analog input signals are below 50% of their minimum signal range. This suggests a defective or loose control cable, or a malfunction in the signal source itself. This can lead to incorrect control inputs and affect drive operation.

Common Causes

  • Broken or loose wiring connection at the drive's analog input terminals (e.g., AI1+, AI1-, AGND).
  • Sensor malfunction or failure causing its output signal to drop below 50% of the minimum configured range (e.g., 4-20mA sensor outputting <2mA, 0-10V sensor outputting <0.5V).
  • Incorrect scaling parameters for the analog input (e.g., P3.3.1.2 for AI1 min value, P3.3.1.3 for AI1 max value) not matching the sensor's output range.
  • Excessive electrical noise or ground loop interference corrupting the low-level analog signal, causing it to fall below the valid threshold.
  • Misconfiguration of the analog input supervision fault threshold (e.g., P3.3.1.4 for AI1 supervision fault threshold).

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Check the physical wiring connections at the drive's analog input terminals (e.g., AI1, AI2) for looseness, corrosion, or damage.

  2. 2

    2. Using a multimeter, measure the voltage or current directly at the sensor's output terminals to confirm the actual signal value.

  3. 3

    3. Verify the analog input parameters (e.g., P3.3.1.1 for AI1 type, P3.3.1.2 for AI1 min value, P3.3.1.4 for AI1 supervision fault threshold) match the connected sensor's specifications.

  4. 4

    4. Trace the analog input cable for damage or breaks, checking continuity from the sensor to the drive's input terminals.

  5. 5

    5. Temporarily connect a known good signal source (e.g., potentiometer, signal generator) to the drive's analog input to test the drive's input circuit functionality.

Browse all codes in this manual (73)
Verified technical data. Last updated: March 2026

Related Faults

Source: Vacon 100 FLOW Application Guide