59

Follower Communication Fault

Vacon · NX All-in-One Application

What does 59 mean?

Communication between the Master and Follower drives has been lost via SystemBus or CAN. This indicates a broken communication link, preventing coordinated operation between the units.

Common Causes

  • Communication failure between a master and a follower drive/device.
  • Incorrect follower address or configuration (e.g., P9-01).
  • Network cabling issue between devices.
  • Follower device powered off or not initialized.
  • Data corruption during follower communication.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Verify the option board parameters related to SystemBus or CAN communication for correct configuration (e.g., node ID, baud rate).

  2. 2

    Inspect the optical fibre cable or CAN cable for physical damage, proper connections, and correct termination between master and follower drives.

Browse all codes in this manual (42)
Verified technical data. Last updated: March 2026