Device changed (different type)
Vacon · NXS NXP
What does 44 mean?
An option board or power unit has been replaced with a device of a different type or power rating. The drive detects this incompatibility and requires a complete reconfiguration. If parameters are not correctly reset and adjusted, the drive may operate incorrectly, become unstable, or fail to start.
Common Causes
- Replacement of an option board with a physically different type (e.g., a Profibus board replaced with an Ethernet board) without updating drive parameters.
- Installation of an option board with a different firmware version or hardware revision than previously configured.
- Power unit replacement with one of a different voltage or current rating, causing hardware mismatch.
- Drive's internal configuration (e.g., parameter P7-01 (Slot X config)) does not match the newly installed hardware.
Repair Steps & Checklist
Click steps to track your progress.
- 1
Power down the drive completely and verify zero voltage on DC bus terminals.
- 2
Identify the recently changed option board or power unit.
- 3
Confirm the type and part number of the newly installed component against the application requirements.
- 4
Review parameter P7-01 (Slot X Configuration) for the slot where the change occurred.
- 5
Adjust parameter P7-01 to "0" (No option board), then power cycle the drive.
- 6
Reconfigure the slot by setting P7-01 to the correct value for the newly installed board type and save parameters.