System Fault

Vacon · X4

What does 1 mean?

This fault indicates an internal microprocessor problem (sub-codes 0, 1, 2) or an incorrect thermistor profile (sub-code 3). These issues point to a fundamental problem with the drive's internal control system that cannot be resolved through basic troubleshooting. The drive requires specialized attention.

Common Causes

  • Internal control board hardware malfunction (e.g., ASIC failure, memory corruption).
  • Processor watchdog timer expiry due to software execution deadlock.
  • Incorrect thermistor type or profile selected in parameter P0-15 (Thermistor Type) causing invalid temperature readings.
  • Damage to control board components from electrical transients or environmental stress (e.g., extreme heat, vibration).
  • Firmware corruption during update process leading to improper initialization.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    1. Record the sub-code displayed on the drive's HMI or through diagnostic software.

  2. 2

    2. Verify parameter P0-15 (Thermistor Type) matches the connected thermistor's specifications.

  3. 3

    3. Perform a factory reset via parameter P0-01 (Parameter Reset) to restore default settings and re-enter required parameters.

  4. 4

    4. Measure the supply voltage at the drive's input terminals (L1, L2, L3) to confirm it is within specified tolerance (e.g., 400V +/-10%).

  5. 5

    5. Replace the control board or the entire drive unit if the fault persists after software and basic power checks.