Wago · Modular I/O System PROFIBUS DP
One or more I/O modules connected to the Fieldbus Coupler have reported receiving incorrect internal bus commands. This indicates a critical communication issue on the internal bus, potentially due to a faulty module, corrupted signals, or a defective coupler, leading to unreliable data exchange.
Click steps to track your progress.
Disconnect the Profibus cable from the coupler to isolate internal bus communication.
Plug the end module into the middle of the node to segment the internal bus and identify the faulty section.
Cycle the coupler's supply voltage (off and on again).
If the I/O LED continues to flash, shift the end module again to further isolate the defective segment.
If only one module is connected to the coupler and the I/O Err LED illuminates, replace the single I/O module or the coupler, as one of them is defective.