Wago · PFC200 PLC
The diagnostic bits S1/S0 or S3/S2 for a digital output channel on module 75x-506 are set to '01'. This indicates either no load is connected to the output channel or a short circuit exists between the output and the +24V supply. This condition prevents the output from functioning as intended and alerts to a wiring issue.
Click steps to track your progress.
Verify a load is physically connected to the digital output channel terminals (e.g., DO1, DO2).
Measure the voltage between the affected output terminal and the +24V supply to check for a short circuit.
Use a multimeter to check for continuity in the load wiring from the output terminal to the load's input.