Yaskawa · E7 Drive
Control data was not received correctly for two seconds over the Modbus connection. This implies a broken Modbus connection or the master device has stopped communicating, preventing proper control and data exchange.
Click steps to track your progress.
1. Verify Modbus communication wiring (A, B, GND) for continuity and proper shielding between the drive and master controller.
2. Confirm that Modbus parameters S5-01 (Drive Address), S5-02 (Baud Rate), and S5-03 (Parity) match the master device settings.
3. Check for proper 120 Ohm termination resistors at the first and last devices on the Modbus network segment.
4. Using a Modbus sniffer or diagnostic software, monitor Modbus traffic to analyze communication integrity and packet loss.
5. Cycle power to both the drive and the Modbus master device to clear any temporary communication glitches.