Yaskawa · F7 Drive
A fault in the CPU's internal Analog-to-Digital converter was detected. This issue typically results from noise or electrical spikes on the control circuit input terminals, impairing the CPU's ability to accurately process internal analog signals.
Click steps to track your progress.
Disconnect all analog input wiring (e.g., A1, A2, A3 terminals) from the drive to isolate external signal influence.
Verify the integrity of grounding connections for both the drive and external analog signal sources to prevent ground loops.
Measure the drive's internal control power supply (e.g., 24VDC output) to ensure it is stable and within specification.
Power cycle the drive, allowing sufficient time for internal components to fully reset (e.g., 60 seconds off).
Inspect the drive's main control board for any visible signs of component damage, contamination, or corrosion near the CPU.