Yaskawa · F7 Drive
A fault with the external Analog-to-Digital converter was detected. This problem is often caused by noise or electrical spikes on the control circuit input terminals, impacting the accurate conversion of external analog input signals.
Click steps to track your progress.
Disconnect all analog input wiring (e.g., A1, A2, A3 terminals) to prevent external signals from influencing the A/D converter.
Verify the input voltage/current for connected analog sensors is within the drive's specified range (e.g., -10V to +10V for A1).
Measure the ground reference (e.g., ACM terminal) for stability relative to the analog signal input terminals using a multimeter.
Inspect the drive's control board for any visible damage, especially around the external A/D converter chip or its associated components.
Power cycle the drive, ensuring all residual power is dissipated (e.g., wait 60 seconds after power-off).