Yaskawa · F7 Drive
A communication error has occurred when the SI-F/G Option Card is designated as the source for run commands or frequency reference (b1-01=3 and/or b1-02=3), and communication with it is lost. This implies a failure in the communication link or configuration with the SI-F/G card. Without proper communication, the Drive cannot receive critical commands or references, leading to a stop.
Click steps to track your progress.
Inspect the communication cable (e.g., Ethernet, DeviceNet, Profibus) connected to the SI-F/G option card for secure connections and physical damage.
Verify the communication parameters (e.g., P5-01, P5-02, P5-03) on the Drive's SI-F/G card match the settings on the master controller.
Confirm the master controller (e.g., PLC) is active and sending run commands/frequency references as expected to the SI-F/G card.
Temporarily cycle power to the Drive and the master controller to reset communication modules.
Check for network activity lights (e.g., Link/Act LEDs) on the SI-F/G card itself to confirm physical layer communication.