Yaskawa · F7 Drive
This fault is triggered when an external condition connected to multi-function digital input terminal S3 activates the Drive's external fault function. The Drive will stop according to its programmed response (ramp, coast, or fast stop). This indicates an issue with the external device or process monitored by S3, potentially leading to unsafe operation if misconfigured.
Click steps to track your progress.
Using a multimeter, measure the voltage state at terminal S3 relative to SN (common) to determine if the external input is active.
Inspect all wiring connected to terminal S3 and the external device for physical damage, corrosion, or loose connections.
Verify the setting of parameter H1-03 (S3 function selection) matches the operational logic and contact type (e.g., '0' for external fault N.C.).
Manually actuate the external switch or sensor connected to S3 to confirm its proper mechanical and electrical operation.
Temporarily disconnect the wire from S3 and observe if the fault clears (ENSURE SAFE OPERATION BEFORE DISCONNECTING SAFETY INPUTS).