Yaskawa · F7 Drive
This fault is triggered when an external condition connected to multi-function digital input terminal S4 activates the Drive's external fault function, causing the Drive to stop. It indicates an issue with the external device or process monitored by S4, which could lead to machine downtime or safety risks if misidentified.
Click steps to track your progress.
Confirm the state of the external device (e.g., limit switch, E-stop button) connected to S4, visually and operationally.
Measure the voltage (e.g., 24VDC) at terminal S4 with respect to SN (common) using a multimeter to confirm its state.
Check the parameter H1-04 (S4 function) setting to ensure it is configured for 'External Fault' and matches the expected contact type.
Examine the cable run to terminal S4 for insulation damage, loose terminals, or incorrect termination at both ends.
Temporarily bypass the external device by jumpering S4 to SN (ONLY IF THE INPUT IS N.O. AND IT IS SAFE TO DO SO) to test the Drive's input.