Detected during rotational Auto-Tuning in vector control (A1-02=2 or 3), this fault indicates that the torque reference exceeded 100% during acceleration. This typically points to an issue with acceleration time, incorrect PG (encoder) pulse data, or an excessive mechanical load on the motor. Exceeding torque limits during tuning will lead to inaccurate motor parameterization and potentially inefficient operation.
Click steps to track your progress.
1. Ensure the motor is completely disconnected from the load when performing rotational Auto-Tuning in vector control mode.
2. Verify all motor nameplate parameters (P2-01 to P2-06) are accurately entered into the Drive.
3. Increase the acceleration time parameter (C1-01) to reduce the torque required for acceleration.
4. If using encoder feedback (A1-02=3), inspect the encoder cabling for proper shielding and secure connections to prevent signal noise.
5. Temporarily increase the Drive's current limit parameter (C4-01) and torque limit (L7-01) if necessary, ensuring not to exceed motor ratings.