AUXFB

PI Aux Lvl Loss (Wire-break detection for PI Aux Feedback Level)

Yaskawa · iQpump1000

What does AUXFB mean?

The analog input programmed for “PI Aux FB Level” (H3-oo = 27) has dropped below 3 mA or risen above 21 mA for longer than 1 second.

Common Causes

  • Faulty transducer for PI Aux FB Level.
  • Wiring for the analog input (H3-oo = 27) is damaged or broken.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Repair or replace the transducer.

  2. 2

    Repair the wiring connected to the analog input assigned to PI Aux FB Level.