SEr

Too Many Speed Search Restarts

Yaskawa · P1000

What does SEr mean?

The drive has attempted to perform a speed search restart multiple times consecutively without success, exceeding the allowed limit. This suggests an underlying issue preventing stable motor operation.

Repair Steps & Checklist

Click steps to track your progress.

  1. 1

    Inspect motor power cable connections at both the Yaskawa P1000 AC Drive output terminals (U, V, W) and the motor terminal box for tightness, corrosion, and visible damage.

  2. 2

    Measure the resistance between each motor phase (U-V, V-W, U-W) using a multimeter and measure insulation resistance from each phase to ground using a megohmmeter to verify motor winding integrity and insulation.

  3. 3

    Verify all critical motor parameters configured in the Yaskawa P1000 AC Drive (e.g., motor rated voltage, current, frequency, RPM, pole count, auto-tuning status) precisely match the connected motor's nameplate data.

  4. 4

    Inspect the mechanical load connected to the motor for any obstructions, excessive friction, or binding that could impede free rotation, and confirm the motor shaft can rotate freely when power is off.

Browse all codes in this manual (60)