Yaskawa · V1000
This fault indicates the drive could not detect the motor's polarity within a pre-set length of time during startup or operation. This is typically caused by a disconnection in the motor coil winding or loose screws on the drive's output terminals. Failure to detect polarity prevents the drive from properly controlling the motor, making operation impossible.
Click steps to track your progress.
1. Disconnect the motor from the drive output terminals (U, V, W or T1, T2, T3).
2. Measure the resistance between each motor phase winding (U-V, V-W, W-U) using a multimeter; readings should be balanced.
3. Measure the insulation resistance from each motor phase (U, V, W) to motor ground using a megohmmeter (megger) at 500VDC (should be >100M Ohms).
4. Verify all motor cable connections at the drive (T1, T2, T3) and the motor terminal box are tight and secure.
5. Check motor parameters P1-01 to P1-08 against the motor nameplate data for exact match.
6. If a spare motor is available, connect it to the drive and attempt to run to isolate the fault to the motor or the drive.